RDC Refrigerated Compressed Air Dryers


RDC Beko Refirgerated Air Dryers

Twin Tower Engineering's economy and compact refrigerated air dryer saves space and uses less energy.  

The RDC comes with an electronic controller that indicates the dew point temperature digitally, monitors the condenser fan via a probe, and controls the condensate drain valve with a timer.

The RDC refrigerated air dryer has an aluminum cooling heat exchanger module allowing for minimum pressure drop resulting in energy savings.



The RDC economy / compact refrigerated air dryer's heat exchanger cools the air causing moisture to condense into liquid water. The water is then collected and drained out of the system leaving only dry air.  A timed condensate drain is standard with all units. The cabinet is state-of-the art in design, with easy-to-remove panels reducing maintenance and costs.

 
RDC REFRIGERATED AIR DRYER SPECIFICATIONS
Model No. Flow Rate Connection Size Dryer Dimensions (in) Weight Operating Voltage Required Pre-filter
  scfm NPT L W H lb    
 RDC 10 10 3/8" 12 14 17 46 115V / 1 Ph S040FWF
 RDC 1515 3/8" 12 14 17 49 115V / 1 Ph S040FWF
 RDC 20 20 1/2" 15 20 19 55 115V / 1 Ph S045FWF
 RDC 35 35 1/2" 15 20 19 62 115V / 1 Ph S050FWF
 RDC 50 50 1/2" 15 20 19 71 115V / 1 Ph S055FWF
 RDC 75 75 1" 14 17 29 75 115V / 1 Ph S100FWF
 RDC 100 100 1 ¼" 14 18 29 86 115V / 1 Ph S100FWF
 RDC 125 125 1 ¼" 14 18 29 88 115V / 1 Ph S100FWF
 RDC 150 150 1 ¼" 14 18 29 90 115V / 1 Ph M010FWF
 RDC 175 175 1½" 22 23 35 119 230V / 1Ph M015FWF
 RDC 220 220 1½" 23 23 35 123 230V / 1Ph M015FWF
 RDC 300 300 2 22 25 38 207 230V / 1Ph M020FWF
All dryers Include timer drain
 
ADC regfigeratated air dryer dimensions table
 

CORRECTION FACTORS

 Operating Pressure (psig) 60 80 100 120 140 160 180 200
 Correction factor0.79 0.91 1.00 1.07 1.13 1.18 1.23 1.27
 
 Inlet Air Temperature (°F) 90 100 110 120 130
 Correction factor1.11 1.00 0.80 0.65 0.53
 
 Ambient Air Temperature (°F) 80 90 100 110 115
 Correction factor1.10 1.07 1.00 0.83 0.70
 
 Pressure Dew Point 38 41 45 50
 Correction factor0.92 1.00 1.07 1.25
   

RDC GENERAL SPECIFICATIONS

 Outlet pressure dew point 41 °F
 Max. inlet air temperature130 °F
 Min. / max. ambient temperature 34 °F / 115 °F

 Max. inlet pressure

   RDC 10 - 50

   RDC 75- 300

 

232 psig

200 psig

 Required Pre-Filtration 1.0 pm
 Recommended Past-Filtration 0.01 pm

FEATURES

  • Aluminum Cooling
    Technology
  • Digital controller
  • Integrated aftercooler
  • Programmable electronic timer drains
  • Compact design
  • Easy installation and operation
  • Less down time
  • Energy savings
  • Environmentally friendly CFC-free R134A refrigerant

TYPICAL APPLICATIONS

  • Paint Booths
  • Instrumentation
  • Laboratory
  • Processing
  • Body Shops
  • Pneumatic Control Systems